Air Flow Meter - A2G-25

Brand: WIKA Instruments Ltd.

For ventilation and air-conditioning.
Features
  • Easy installation
  • User-friendly display
  • Easy-to-read LCD display
  • Temperature compensated
  • Output signals for differential pressure and air volume flow

Specifications

Measuring Element

  • Piezo Measuriing cell

Measuring Range

  • Modbus® version: 0 ... 2,500, 0 ... 7,000 Pa
  • Analogue output signal (0 ... 10 V/4 ... 20 mA): 0 ... 1,000, 0 ... 2,000, 0 ... 5,000, 0 ... 7,000 Pa

Accuracy

  • All data refer to the above mentioned pressure range
  • 0 to 1,000 Pa: ±2 Pa ±1.5 %
  • 0 to 2,000 Pa: ±2 Pa ±1.5 %
  • 0 to 2,500 Pa: ±2 Pa ±1.5 %
  • 0 to 5,000 Pa: ±2 Pa ±1.5 %
  • 0 to 7,000 Pa: ±2 Pa ±1.5 %

Units (adjustable in the Menu)

  • Differential pressure: Pa, kPa, mbar, inWC, mmWC
  • Air flow: m3/h, m3/s, l/s, cfm

Process Connection

  • For hoses with inner diameter 4 or 6 mm

Power Supply UB

  • AC 24 V or DC 24 V ±10 %

Output Signal

  • POUT: 4 ... 20 mA, load R minimum 1 kΩ linear to the set output unit
  • VOUT: 4 ... 20 mA, load R minimum 1 kΩ linear to the set output unit
  • POUT: DC 0 ... 10 V, load R minimum 1 kΩ linear to the set output unit
  • VOUT: DC 0 ... 10 V, load R minimum 1 kΩ linear to the set output unit

Electrical Connection

  • Screw terminals max. 1.5 mm2
  • Cover: PG
  • Cable gland M16

Current Consumption

  • < 1.0 W (DC 0 ... 10 V), < 1.2 W (4 ... 20 mA), < 1.3 W (Modbus®)

Case

  • Cover: Polycarbonate (PC)
  • Plastic (ABS)

Type of Mounting

  • Wall mounting

Zero Adjustment

  • Push button on the printed circuit board or via Modbus® register

Permissible Temperatures

  • Medium Temperature: -10 ... +50° C, version with automatic zero point setting: -5 ... +50° C
  • Ambient Temperature: -20 ... +70° C

Ingress Protection

  • IP54

Weight

  • 150 g

Documentation

show more